The building is in fair overall condition. One high-risk defect (honeycombing on a ground-floor column) needs a structural engineer's review before further loading. Two medium and two low-risk items can be fixed in the normal course of finishing works.
| # | Finding | Location | Risk |
|---|---|---|---|
| 1 | Honeycombing on column face | Ground floor, column C3 | High |
| 2 | Exposed reinforcement, low concrete cover | First-floor slab edge, east side | Medium |
| 3 | Hairline cracks in plaster | First floor, bedroom 2 wall | Medium |
| 4 | Uneven floor screed (10 mm gap under a 2 m straightedge) | Living room | Low |
| 5 | Minor damp staining on ceiling | Second floor, bathroom | Low |
What we saw: exposed stone and voids over roughly 0.4 m of the lower column face, with reinforcement partly visible. Why it matters: voids reduce the load the column can carry and let moisture reach the steel. Recommended action: rebound-hammer and ultrasonic testing, review by a structural engineer, then repair with approved non-shrink grout. Do not load the column further until cleared.
What we saw: rust-stained bars close to the slab soffit. Why it matters: thin cover allows corrosion and later spalling. Recommended action: clean the steel, apply a rust-inhibiting primer and repair with polymer-modified mortar.
What we saw: vertical cracks about 0.3 mm wide, running about 1.2 m. Why it matters: likely shrinkage at this width, but it should be monitored for movement. Recommended action: mark the ends and re-check in 3 months. Fill and repaint if unchanged.
| Foundation | No visible settlement or cracking at accessible points. |
| Columns and beams | One defective column (C3). Others sound on visual inspection. |
| Slabs | Level and generally well cast. Low cover at the east edge of the first floor. |
| Walls | Block courses are straight. Minor plaster cracking in bedroom 2. |
| Finishes | Screed unevenness in the living room. |
| Services | Electrical conduits are properly fixed. Slight damp near the bathroom plumbing. |
Visual inspection of areas safely accessible on the day. No destructive testing unless stated. This report does not replace specialist investigation where recommended. This is a sample, so none of these findings relate to a real building.
Sample Engineer, B.Eng, M.Eng · COREN No. 00000 (sample) · Signature: ________ · Date: 14 March 2026