Structural Integrity & Quality Audit Report

Report ref: VG-AUD-0247 · Date of inspection: 12 March 2026
Site: Three-storey residential building, Gwarinpa, Abuja
Prepared for: Mr A. Okoye (sample client), based abroad
Inspected by: Sample Engineer, B.Eng, M.Eng, COREN No. 00000 (sample)

1. Summary of findings

The building is in fair overall condition. One high-risk defect (honeycombing on a ground-floor column) needs a structural engineer's review before further loading. Two medium and two low-risk items can be fixed in the normal course of finishing works.

#FindingLocationRisk
1Honeycombing on column faceGround floor, column C3High
2Exposed reinforcement, low concrete coverFirst-floor slab edge, east sideMedium
3Hairline cracks in plasterFirst floor, bedroom 2 wallMedium
4Uneven floor screed (10 mm gap under a 2 m straightedge)Living roomLow
5Minor damp staining on ceilingSecond floor, bathroomLow

2. Defect schedule

Finding 1: Honeycombing on column C3 High Voids / honeycombing
Illustration only. Not a photograph.

What we saw: exposed stone and voids over roughly 0.4 m of the lower column face, with reinforcement partly visible. Why it matters: voids reduce the load the column can carry and let moisture reach the steel. Recommended action: rebound-hammer and ultrasonic testing, review by a structural engineer, then repair with approved non-shrink grout. Do not load the column further until cleared.

Finding 2: Low concrete cover at slab edge Medium Cover about 10 mm (specified: 25 mm)
Illustration only. Not a photograph.

What we saw: rust-stained bars close to the slab soffit. Why it matters: thin cover allows corrosion and later spalling. Recommended action: clean the steel, apply a rust-inhibiting primer and repair with polymer-modified mortar.

Finding 3: Hairline cracks in plaster Medium
Illustration only. Not a photograph.

What we saw: vertical cracks about 0.3 mm wide, running about 1.2 m. Why it matters: likely shrinkage at this width, but it should be monitored for movement. Recommended action: mark the ends and re-check in 3 months. Fill and repaint if unchanged.

3. Observations by area

FoundationNo visible settlement or cracking at accessible points.
Columns and beamsOne defective column (C3). Others sound on visual inspection.
SlabsLevel and generally well cast. Low cover at the east edge of the first floor.
WallsBlock courses are straight. Minor plaster cracking in bedroom 2.
FinishesScreed unevenness in the living room.
ServicesElectrical conduits are properly fixed. Slight damp near the bathroom plumbing.

4. Recommendations, in priority order

  1. Immediately: structural engineer's review and testing of column C3.
  2. Within 2 weeks: repair the low-cover slab edge and trace the bathroom leak.
  3. Before painting: fill the plaster cracks and re-level the screed.
  4. In 3 months: re-inspect the monitored cracks.

5. Limitations

Visual inspection of areas safely accessible on the day. No destructive testing unless stated. This report does not replace specialist investigation where recommended. This is a sample, so none of these findings relate to a real building.

6. Sign-off

Sample Engineer, B.Eng, M.Eng · COREN No. 00000 (sample) · Signature: ________ · Date: 14 March 2026